BS5308 Part1 Instrumentation Cable Polyethylene Insulated

VDE Ref Code
 
PVC Sheath Version LSOH Sheath Version:
RE-2Y(St)Y (Overall Screen) RE-2Y(St)H (Overall Screen)
RE-2Y(St)Y PiMF(Individual Screen+Overall Screen) RE-2Y(St)HPiMF(Individual Screen+Overall Screen)
RE-2Y(St)Y-SWA(Overall Screen+Steel Wire Armour) RE-2Y(St)-SWA(Overall Screen+Steel Wire Armour)
RE-2Y(St)Y PiMF-SWA(Individual Screen+Overall Screen+Steel Wire Armour) RE-2Y(St)HPiMF-SWA(Individual Screen+Overall Screen+ Steel Wire Armour
Construction
Construction: Annealed solid copper(Class 1),stranded(Class2), Binder tape:A 23 micron p.e.t.p.tape applied with a
or fiexible(Class 5) to BS5360 . minimum 50% overlap.
Insulation: Polyethylene to BS 6234 Type 03. Collective screen:
Pair identification: Aluminium/p.e.t.p.laminated tape applied with the metallic side
a)Collectively screened cables:Colour coded in down in electrical contact with a 0.5mm 2 tinned copper
. accordance with Colour Code Chart 1 on page3 drain wire over the p.e.t.p.binder tape.
b)Individually screened pairs:One blue core and one Outer protection:
  black core in each pair.Pairs identified by numbered Type 1 Extruded flame retardant PVC sheath.
  screen isolation tape. Type 2 Extruded polyethylene bedding,alvanised steel
Pair screens   wire armour,extruded flame retardant PVC sheath.
Aluminium/p.e.t.p.Laminated tape applied with the metallic Minimum bending radius:
side down in electrical contact with a 0.5 mm 2 tinned copper drain wire. Type 1 8 x diameter.
A 23 micron isolation tape is applied over the screening tape with a Type 2 12xdiameter.
minimum 50% overlap.  
Voltage rating Temperature rating
300 volt core to earth and 500 volt core to core at maximum During Operation:-40 ℃+70℃
temperature of 65 ℃ During Operation:-0 ℃+50℃
These cables are not for direct connection to the public mains supply  
   
Electrical characteristics  
Parameter
Note
Unit
Conductor size
0.5mm 2
(1/0.8mm)
0.5mm 2
(16/0.2mm)
0.75mm 2
(24/0.2mm)
1.0mm 2
(1/1.13mm)
1.5mm 2
(7/0.53mm)
Conductor resistance
max.

Ω/Km

36.8
39.7
26.5
18.2
12.3
Insulation resistance
max.
GΩxKm
5
5
5
5
5
Mutual capacitance at 1 kH
-One pair and two pair(Quad)cables with collective screen and all
cables with individually screened pairs
-Cables with only collective screen except one pair and two pair(Quad)
max.
pF/m
115
75
115
75
115
75
115
75
115
85
Capacitance unbalance at 1 kHz
max.
pF/250m
250
250
250
250
250
Inductance/resistance ratio(L/R)
max.
μH/Ω
25
25
25
25
25
Test voltage
(Core:core)
-
V
V
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
(Core:core)
Rated voltage
max.
V
300/500
300/500
300/500
300/500
300/500

MULTIPAIR INSTRUMENTATION CABLES(UNARMOURED)
TO BS 5308 PART 1-COLLECTIVELY SCREENED

MULTIPAIR INSTRUMENTATION CABLES(UNARMOURED)TO BS 5308
PART 1 TYPE 1-INDIVIDUAL PAIR AND COLLECTIVELY SCREENED

MULTIPAIR INSTRUMENTATION CABLES(ARMOURED)
TO BS 5308 PART 1 TYPE 2-COLLECTIVELY SCREENED

MULTIPAIR INSTRUMENTATION CABLES(ARMOURED)TO
BS 5308 PART 1 TYPE 2-INDIVIDUAL PAIR AND COLLECTIVELY SCREENED

COLOUR CODE CHART 1